This tool estimates voltage drop in an electrical circuit. The “NEC data” tab performs calculations using resistance and reactance values from the National Electrical Code. The “Estimated resistance” tab uses resistance values derived from the selected wire size. For custom inputs—such as data from alternative standards or specific wire manufacturers—use the “Other” tab to enter your own resistance or impedance values.
Voltage Drop
—
Drop Percentage
—
Voltage at Load
—
When electric current flows through a conductor, it is driven by voltage but must overcome opposition within the wire. The resulting loss of voltage due to this opposition is known as voltage drop. In alternating current (AC) systems, this opposition is called impedance, which combines resistance and reactance (the effect of changing electric fields). In direct current (DC) systems, the opposition is simply referred to as resistance.
If voltage drop becomes too high, it can lead to problems such as dim or flickering lights, inefficient heating, and motors overheating or failing. To avoid these issues, it's generally recommended to keep voltage drop below 5% when the circuit is fully loaded. This can be managed by choosing appropriate wire types and sizes, and by being mindful when using extension cords or similar setups.
Several key factors influence voltage drop:
1. Wire Material
Different materials conduct electricity with varying efficiency. Metals like silver, copper, gold, and aluminum are highly conductive, but copper and aluminum are most commonly used due to cost. Copper conducts better than aluminum, meaning it produces less voltage drop for the same size and length.
2. Wire Size
Thicker wires (larger diameter) have lower resistance and therefore less voltage drop compared to thinner wires of the same length. In the American Wire Gauge (AWG) system, reducing the gauge number increases the diameter and cross-sectional area. In the metric system, the gauge corresponds directly to the wire's diameter in millimeters.
3. Wire Length
Longer wires result in greater voltage drop, while shorter runs minimize it. This becomes especially important in long-distance applications, such as wiring to detached buildings or outdoor equipment, though it's usually less of a concern in typical household circuits.
4. Current Load
Higher current flowing through a wire increases voltage drop. The maximum current a wire can safely carry is called its ampacity (short for ampere capacity), which represents how many electrons can pass through without overheating.
Ampacity depends on several conditions, including the wire material, whether the current is AC (and its frequency), and the surrounding temperature. When cables are grouped together, heat buildup can further impact ampacity and voltage drop, which is why there are strict guidelines for cable bundling.
When selecting cables, two main considerations apply. First, the wire must safely handle the expected current without overheating, even under extreme conditions. Second, it must provide effective grounding to ensure safety—both by limiting dangerous voltage exposure and by allowing fault currents to quickly trigger protective devices like fuses.
Ohm's Law is a very basic law for calculating voltage drop:
Vdrop = I·R
where:
I: the current through the wire, measured in amperes
R: the resistance of the wires, measured in ohms
The resistance of the wires is often measured and given as length-specific resistance, normally in the unit of ohms per kilometer or ohms per 1000 feet. Also, the wire is round-tripped. Therefore, the formula for a single-phase or direct current circuit becomes:
Vdrop = 2·I·R·L
The formula for a three-phase circuit becomes:
Vdrop = √3·I·R·L
where:
I: the current through the wire
R: the length-specific resistance of the wires
L: the one-way length
American Wire Gauge (AWG) is a wire gauge system used predominantly in North America for the diameters of round, solid, non-ferrous, electrically conducting wire. The following is a list of typical AWG wires and their sizes:
| AWG | Diameter | Turns of wire | Area | Copper resistance | ||||
|---|---|---|---|---|---|---|---|---|
| inch | mm | per inch | per cm | kcmil | mm2 | Ω/km | Ω/1000ft | |
| 0000 (4/0) | 0.4600 | 11.684 | 2.17 | 0.856 | 212 | 107 | 0.1608 | 0.04901 |
| 000 (3/0) | 0.4096 | 10.404 | 2.44 | 0.961 | 168 | 85.0 | 0.2028 | 0.06180 |
| 00 (2/0) | 0.3648 | 9.266 | 2.74 | 1.08 | 133 | 67.4 | 0.2557 | 0.07793 |
| 0 (1/0) | 0.3249 | 8.252 | 3.08 | 1.21 | 106 | 53.5 | 0.3224 | 0.09827 |
| 1 | 0.2893 | 7.348 | 3.46 | 1.36 | 83.7 | 42.4 | 0.4066 | 0.1239 |
| 2 | 0.2576 | 6.544 | 3.88 | 1.53 | 66.4 | 33.6 | 0.5127 | 0.1563 |
| 3 | 0.2294 | 5.827 | 4.36 | 1.72 | 52.6 | 26.7 | 0.6465 | 0.1970 |
| 4 | 0.2043 | 5.189 | 4.89 | 1.93 | 41.7 | 21.2 | 0.8152 | 0.2485 |
| 5 | 0.1819 | 4.621 | 5.50 | 2.16 | 33.1 | 16.8 | 1.028 | 0.3133 |
| 6 | 0.1620 | 4.115 | 6.17 | 2.43 | 26.3 | 13.3 | 1.296 | 0.3951 |
| 7 | 0.1443 | 3.665 | 6.93 | 2.73 | 20.8 | 10.5 | 1.634 | 0.4982 |
| 8 | 0.1285 | 3.264 | 7.78 | 3.06 | 16.5 | 8.37 | 2.061 | 0.6282 |
| 9 | 0.1144 | 2.906 | 8.74 | 3.44 | 13.1 | 6.63 | 2.599 | 0.7921 |
| 10 | 0.1019 | 2.588 | 9.81 | 3.86 | 10.4 | 5.26 | 3.277 | 0.9989 |
| 11 | 0.0907 | 2.305 | 11.0 | 4.34 | 8.23 | 4.17 | 4.132 | 1.260 |
| 12 | 0.0808 | 2.053 | 12.4 | 4.87 | 6.53 | 3.31 | 5.211 | 1.588 |
| 13 | 0.0720 | 1.828 | 13.9 | 5.47 | 5.18 | 2.62 | 6.571 | 2.003 |
| 14 | 0.0641 | 1.628 | 15.6 | 6.14 | 4.11 | 2.08 | 8.286 | 2.525 |
| 15 | 0.0571 | 1.450 | 17.5 | 6.90 | 3.26 | 1.65 | 10.45 | 3.184 |
| 16 | 0.0508 | 1.291 | 19.7 | 7.75 | 2.58 | 1.31 | 13.17 | 4.016 |
| 17 | 0.0453 | 1.150 | 22.1 | 8.70 | 2.05 | 1.04 | 16.61 | 5.064 |
| 18 | 0.0403 | 1.024 | 24.8 | 9.77 | 1.62 | 0.823 | 20.95 | 6.385 |
| 19 | 0.0359 | 0.912 | 27.9 | 11.0 | 1.29 | 0.653 | 26.42 | 8.051 |
| 20 | 0.0320 | 0.812 | 31.3 | 12.3 | 1.02 | 0.518 | 33.31 | 10.15 |
| 21 | 0.0285 | 0.723 | 35.1 | 13.8 | 0.810 | 0.410 | 42.00 | 12.80 |
| 22 | 0.0253 | 0.644 | 39.5 | 15.5 | 0.642 | 0.326 | 52.96 | 16.14 |
| 23 | 0.0226 | 0.573 | 44.3 | 17.4 | 0.509 | 0.258 | 66.79 | 20.36 |
| 24 | 0.0201 | 0.511 | 49.7 | 19.6 | 0.404 | 0.205 | 84.22 | 25.67 |
| 25 | 0.0179 | 0.455 | 55.9 | 22.0 | 0.320 | 0.162 | 106.2 | 32.37 |
| 26 | 0.0159 | 0.405 | 62.7 | 24.7 | 0.254 | 0.129 | 133.9 | 40.81 |
| 27 | 0.0142 | 0.361 | 70.4 | 27.7 | 0.202 | 0.102 | 168.9 | 51.47 |
| 28 | 0.0126 | 0.321 | 79.1 | 31.1 | 0.160 | 0.0810 | 212.9 | 64.90 |
| 29 | 0.0113 | 0.286 | 88.8 | 35.0 | 0.127 | 0.0642 | 268.5 | 81.84 |
| 30 | 0.0100 | 0.255 | 99.7 | 39.3 | 0.101 | 0.0509 | 338.6 | 103.2 |
| 31 | 0.00893 | 0.227 | 112 | 44.1 | 0.0797 | 0.0404 | 426.9 | 130.1 |
| 32 | 0.00795 | 0.202 | 126 | 49.5 | 0.0632 | 0.0320 | 538.3 | 164.1 |
| 33 | 0.00708 | 0.180 | 141 | 55.6 | 0.0501 | 0.0254 | 678.8 | 206.9 |
| 34 | 0.00630 | 0.160 | 159 | 62.4 | 0.0398 | 0.0201 | 856.0 | 260.9 |
| 35 | 0.00561 | 0.143 | 178 | 70.1 | 0.0315 | 0.0160 | 1079 | 329.0 |
| 36 | 0.00500 | 0.127 | 200 | 78.7 | 0.0250 | 0.0127 | 1361 | 414.8 |
| 37 | 0.00445 | 0.113 | 225 | 88.4 | 0.0198 | 0.0100 | 1716 | 523.1 |
| 38 | 0.00397 | 0.101 | 252 | 99.3 | 0.0157 | 0.00797 | 2164 | 659.6 |
| 39 | 0.00353 | 0.0897 | 283 | 111 | 0.0125 | 0.00632 | 2729 | 831.8 |
| 40 | 0.00314 | 0.0799 | 318 | 125 | 0.00989 | 0.00501 | 3441 | 1049 |